Which of the operating principles listed would apply to a single-element, thermo-hydraulic, feed water regulator?
- AA failure of the regulator pressure actuating system, such as from a leaky bellows, will tend to close the feed water valve. ✓
- BThe regulator is designed to always maintain a constant water level throughout the entire boiler load range.
- CThe water side line leading to the inner tube is normally insulated.
- DThe pressure in the inner tube acts upon the bellows of the regulator.
Correct answer: A) A failure of the regulator pressure actuating system, such as from a leaky bellows, will tend to close the feed water valve.