On some electrical generating equipment one outboard bearing pedestal is insulated from the bedplate. This should be checked with a millivolt meter and a jumper. With the millivolt meter connected between the shaft and the bedplate, how should the jumper be used?

  1. AIt should be placed from one end of the shaft to the other to eliminate shaft currents.
  2. BIt is used to short the + and - in a D.C. generator or Phase A and Phase C in an alternator to eliminate the effects of CEMF.
  3. CIt should be placed across the insulating block to increase the shaft current to a point where it can be measured with the millivolt meter.
  4. DIt should be placed from the shaft to the pedestal while one reading is taken, then removed to take a second reading. This eliminates the insulating effect of the bearing. ✓

Correct answer: D) It should be placed from the shaft to the pedestal while one reading is taken, then removed to take a second reading. This eliminates the insulating effect of the bearing.