In accordance with Coast Guard Regulations (46 CFR), a circuit breaker located in the machinery space and installed in a 440V AC system must __________.

  1. Abe dependent upon mechanical cooling to operate within its rating
  2. Bhave a long-time delay trip element set above the continuous current rating of the trip element or the circuit breaker frame
  3. Chave an interrupting rating sufficient to interrupt the maximum asymmetrical short-circuit current available at the point of application ✓
  4. Dall of the above

Correct answer: C) have an interrupting rating sufficient to interrupt the maximum asymmetrical short-circuit current available at the point of application

USCG question bank (2008) · Electricity – Question Bank Book 12 · pass mark 70%