A direct acting, pneumatically controlled governor for a diesel engine operates in a range of 10 to 50 psi. The fuel rack position is at 20 millimeters when the governor air pressure is 30 psi. If the governor air pressure changes to 20 psi, the fuel rack setting will change to __________.

  1. A13 millimeters ✓
  2. B17 millimeters
  3. C22 millimeters
  4. D24 millimeters

Correct answer: A) 13 millimeters

USCG question bank (2008) · Motor Plants and Auxiliary Boilers – Question Bank Book 14 · pass mark 70%