When an auxiliary boiler is on the line, the output of the flame scanner can be checked by placing a micro ammeter in series with the photoelectric cell circuit. The readings on high fire should be __________.

  1. Ahigher than those at low fire ✓
  2. Bequal to those at low fire
  3. Clower than those at low fire
  4. Dlower than those at low fire, but the generated voltage will be higher

Correct answer: A) higher than those at low fire

USCG question bank (2008) · Motor Plants and Auxiliary Boilers – Question Bank Book 14 · pass mark 70%