Two AC generators are operating in parallel and both are equipped with automatic voltage regulators. While standing watch, one generator is noted as having a greater lagging kvar value. In order to equalize the kvars between the generators you should __________.
- Aincrease the speed of the generator with the largest kvar while decreasing the other generator speed
- Bdecrease the speed of the generator with the largest kvar while increasing the other generator speed
- Cincrease the voltage of the generator with the largest kvar while decreasing the other generator voltage
- Ddecrease the voltage of the generator with the largest kvar while increasing the other generator voltage ✓
Correct answer: D) decrease the voltage of the generator with the largest kvar while increasing the other generator voltage