A three-phase alternator is operating at 450 volts with the switchboard ammeter indicating 300 amps. The kw meter currently indicates 163.6 KW, with a power factor of 0.7. If the power factor increases to 0.8, the KW meter would then read __________.
- A181.4 KW
- B187.0 KW ✓
- C194.2 KW
- D201.4 KW
Correct answer: B) 187.0 KW