A three-phase alternator is operating at 450 volts with the switchboard ammeter indicating 300 amps. The kw meter currently indicates 163.6 KW, with a power factor of 0.7. If the power factor increases to 0.8, the KW meter reading would increase by __________.

  1. A17.8 KW
  2. B23.2 KW ✓
  3. C30.6 KW
  4. D37.8 KW

Correct answer: B) 23.2 KW