An alternator switchboard has a synchroscope and synchronizing lamps. If the synchroscope is broken, which of the steps listed is the most essential before an alternator can be paralleled with the bus?

  1. AThe breaker should be closed when one synchronizing lamp is dark and the other is bright.
  2. BThe breaker should be closed when both synchronizing lamps are bright.
  3. CThe frequency meter should be used to determine that the incoming alternator frequency is slightly higher than the bus. ✓
  4. DA portable phase sequence indicator must be used to verify the information from the lamps.

Correct answer: C) The frequency meter should be used to determine that the incoming alternator frequency is slightly higher than the bus.

USCG question bank (2008) · Electricity – Question Bank Book 12 · pass mark 70%