A refrigeration system is found to be too warm, and the compressor is not operating. A service check determines the compressor suction pressure to be above the normal cut-in point, with a normal head pressure, and high evaporator superheat. Which of the following could be the cause of the problem?
- AA solenoid valve has failed closed.
- BA solenoid valve is stuck open.
- CThe suction pressure control contacts are stuck open. ✓
- DCooling water flow to the condenser is excessive.
Correct answer: C) The suction pressure control contacts are stuck open.