A refrigeration system is found to be too warm, and the compressor is not operating. A service check determines the compressor suction pressure to be above the normal cut-in point, with a normal head pressure, and high evaporator superheat. Which of the following could be the cause of the problem?

  1. AA solenoid valve has failed closed.
  2. BA solenoid valve is stuck open.
  3. CThe suction pressure control contacts are stuck open. ✓
  4. DCooling water flow to the condenser is excessive.

Correct answer: C) The suction pressure control contacts are stuck open.

USCG question bank (2008) · Engineering General Subjects – Question Bank Book 11 · pass mark 70%