According to SOLAS II-2 (19),if in cargo spaces for carriage of dangerous goods is fitted electrical equipment without certificate under IEC 60092
- Athere should not be stowage and carrying hazardous cargo.
- Bthe electrical system shall be completely isolated (e.g. by removal of links in the system, other than fuses). ✓
- Cit shall be completely isolated (e.g. by removal the fuses).
- Dit shall be completely isolated (e.g. by switching off).
Correct answer: B) the electrical system shall be completely isolated (e.g. by removal of links in the system, other than fuses).